Formula

  1. Load energy = sum of (running W x duty x hours on) for each appliance.
  2. Idle energy = the unit's idle draw (W) x target hours.
  3. Required battery = (load energy + idle energy) / (usable depth x inverter efficiency). Defaults: % depth, 85% efficiency.
  4. Runtime = target hours x battery Wh / required battery.
  5. Running load = sum of running W of everything on at once. Must be at or under the continuous AC rating.
  6. Start surge = the largest single start surge plus the running W of everything else. Must be at or under the unit's surge rating, or the result is NO.

Capacity uses nameplate Wh. The vendor's stated usable Wh is shown for reference and is not applied twice.